Plumbing & Heating report

38 Pennington Drive Weybridge

Report by: J. Wegener
Report date: 16th December 2025

Issue number: 1

Water pressure

System is fitted with a pressurised hot water cylinder that needs 3bar of incoming water pressure, the incoming main is only 2.5bar of pressure

Issue number: 2

Hot water

The system needs a secondary return, as the furthest hot tap is over 12m from the cylinder.
There is a pipe connected to the secondary return connection on the cylinder, but there is no pump or check value

Issue number: 3

Heating

Magnetic filter has been fitted to the return to the cylinder and not the heating system

Issue number: 4

Heating

The expansion vessel incorrectly fitted to the secondary return on the cylinder

Issue number: 5

Underfloor heating

There are some cold spots on the floor, would recommand having a thermal imaging firm in to detamin the routes of the pipes

Issue number: 6

Water softener

Check values have not been fitted

Issue number: 7

General

Pipes have not been insulated.
Traps have not been fitted to the wastes within the garage